INSULATOR TRANSMISSION & DISTRIBUTION; LINE POST TYPE;34.5 KV NOM; 175 KV DRY; 150 KV WET FLASHOVER;12.5 KN CANTILEVER STRENGTH;POLYMER INSULATO;HORIZONTAL 34.5 KV NOM; FOR OVERHEAD LINE APPLICATION; MANUFACTURED; TESTED AND MARKED AS PER 15-SDMS-02 REV.01 SEC STANDARD ANSI C30 SERIES OF STANDARDS OR EQUIVALENT IEC STANDARDS WITH THE FOLLOWING MINIMUM REQUIREMENTS; OPERATING VOLTAGE; 34.5 KV; IMPULSE POSITIVE FLASHOVER VOLTAGE; 290 KV; IMPULSE NEGATIVE FLASHOVER VOLTAGE; 380 KV; 60 HZ WET FLASHOVER VOLTAGE; 150 KV; 60 HZ DRY FLASHOVER VOLTAGE; 175 KV;TENSION STRENGTH; 22.2 KN; CANTILEVER STRENGTH; 12.5 KN; LEAKAGE DISTANCE; 1381 MM;INSULATOR; COMPLETE WITH BASE MOUNTING BRACKET INSULATOR; 3/4 MOUNTING STUD (SHALL BE SEPARATE AND DETACHABLE THREADED TYPE STUD);AND CLAMPTOP CLAMP END FITTINGS SHALL BE FOR OCTOGONAL STEEL POLE CONSTRUCTION AND SINGLE PENGUIN / AW (4/0 AWG) CONDUCTOR PER PHASE APPLICATION. LINE END FITTINGS SHALL BE SINGLE TRUNNION DUCTILE IRON WITH CLAMPS SUITABLE FOR SINGLE PENGUIN CONDUCTOR. INSTALLATION DETAILS OF INSULATORS WILL BE AS PER DRAWING NO; ATTACH-001; SHEET-001; THE MOUNTING BRACKET SHALL BE SUITABLE TO INSTALL ON THE OCTAGONAL STEEL POLE.